- Function: 2-channel, changeover contact
- Certificates
- ATEX IECEx II(1)G [Ex ia Ga] IIC, II(1) D [Ex ia Da] IIIC, II3G Ex ec nC IIC Gc
- DNV
- For ambient temperatures -40 to 140°F (-40 to 60°C)چ
The E+H RLN42 NAMUR isolating amplifier is designed for operation of proximity switches according to EN 60947-5-6 (NAMUR) as well as open and mechanical contacts with resistive coupling elements. It has a universal power supply (24 to 230 V AC/DC) and one relay output (changeover) per channel. The device is approved for intrinsically safe (Ex i) circuits up to zone 0 (gas) and zone 20 (dust) in the Ex area. RLN42 can be used in safety equipment up to SIL 2 in accordance with IEC 61508.
This isolating amplifier monitors the input circuits for line faults, such as line breaks and short-circuits (LFD). It is disengageable. Contains input for proximity sensors acc. to NAMUR (EN 60947-5-6); floating contacts or contacts with resistance circuit. The output-side relay contacts as signal output, direction of action can be selected via DIP switches. Configurable with resistive coupling element for line monitoring of mechanical switching contacts.
Reviews
Clear filtersThere are no reviews yet.